Type | Model | Feature | Model | Capacity (L) | Operating Temp. Range (deg.C) | Cooling Capacity (W) (Liquid deg.C) |
Cooling Type | External Circulation | Max Flow Rate (L/min) (50/ 60Hz) |
Max Lift (m) (50/ 60Hz) |
Bath | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Refrige - rator |
Peltier Device | Closed | Open | in- clude |
not in- clude |
|||||||||||
Ex- ternal Open Circu- lation |
Cool Line | Temp. Adjustment Accuracy ±0.1deg.C | CLH302 | 1.5 | -10 to +80 | 450 (at15) |
● | ● | 5.4 /6.2 |
3.5 /5.0 |
● | |||||
CLH401 | 3 | -15 to +80 | 600 (at15) |
● | ● | 5.4 /6.3 |
3.7 /5.3 |
● | ||||||||
CLH610 | 3 | -15 to +80 | 785 (at15) |
● | ● | 6.7 /7.8 |
6.2 /8.7 |
● | ||||||||
Cool Line | Refrige - rator ON-OFF |
CLS302 | 1.5 | -10 to Room Temp. | 450 (at15) |
● | ● | 5.4 /6.2 |
3.5 /5.0 |
● | ||||||
Coolnics Circulator | Freon -free |
CTA402(S) /CTA412(S) |
- | 0 to +70 | 83 (at20) |
● | ● | 8 (50Hz) |
- | ● | ||||||
CTA802(S) /CTA812(S) |
- | 0 to +70 | 163 (at20) |
● | ● | 11 (50Hz) |
- | ● | ||||||||
CTW402(S) /CTW412(S) |
- | -10 to +70 | 126 (at20) |
● (Water Cooling) | ● | 8 (50Hz) |
- | ● | ||||||||
CTW802(S)/ CTW812(S) |
- | -10 to +70 | 250 (at20) |
● (Water Cooling) | ● | 11 (50Hz) |
- | ● | ||||||||
Ex- ternal Closed Circu- lation |
Neocool Circulator | Temp. Adjustment Accuracy ±0.1deg.C | CFA302 | 13 | -10 to +60 | 370 (at10) |
● | ● | 8.9 /10.3 |
6.6 /9.0 |
● | |||||
CFA611 | 6 | -10 to +80 | 850 (at10) |
● | ● | 12.7 /14.4 |
10 /13.4 |
● | ||||||||
CFW611 | 6 | -10 to +80 | 1,300 (at10) |
● | ● | 12.7 /14.4 |
10 /13.4 |
● | ||||||||
Neocool Circulator | Refrige - rator ON-OFF |
CF301 | 3 | -20 to Room Temp. | 450 (at10) |
● | ● | 6.3 /7.2 |
4.0 /5.6 |
● | ||||||
CF800 | 14 | -20 to Room Temp. | 910 (at10) |
● | ● | 10.0 /11.8 |
10.3 /14.3 |
● | ||||||||
Floor-Mount, Solvent Collection, Built-in Vacuum Pump, Outside Interlock Lab Cube | Refrige - rator ON-OFF, Solvent Collector and Built-in Vacuum Pump and Outside Interlock |
CF321P | 3 | -20 to Room Temp. | 400 (at10) |
● | ● | 9.1 /8.9 |
4.8 /5.5 |
● | ||||||
Neocool Aspirator (Depressu -rization, Cooling) |
CF800P | 14 | -20 to Room Temp. | 910 (at0) |
● | ● | 10 /11.8 |
10.3 /14.3 |
● | |||||||
Floor-Mount Lab Cube | High power and lower power consumption type with inverter | CFE820 | 13 | -20 to +20 | 1100 (at0) |
● | ● | 8.2 /9.5 |
9.5/13 | ● | ||||||
CFE920 | ● | ● | 12 /14 |
● | ||||||||||||
Floor-Mount, Precise control | High power type with inverter | CFI701 | 5 | 5 to 30 | 1000W (at20) | ● | ● | 15 /18 |
35 /48 |
● | ||||||
CFI911 | 1600W (at20) | ● | ● | 22 /26 |
52 /65 |
● | ||||||||||
CFI1111 | 2700W (at20) | ● | ● | ● | ||||||||||||
Inverterr | CFI601 | 5 | -10 to 30 | 1000W (at20) | ● | ● | 15/17 | 10/14 | ● | |||||||
CFI811 | 1800W (at20) | ● | ● | ● | ||||||||||||
CFI1011 | 2900W (at20) | ● | ● | ● | ||||||||||||
CIW1100 | 17 | 0 to 80 | 3200W (at20) | ● (Water Cooling) | ● | 19 /22 |
14.5 /20.5 |
● |